CENTRIFUGAL TURRET TC
TC60/6
The TC series is used for direct or ducted rooftop suction, wherever large volumes of air need to be moved with modest heads. The construction of this series, equipped with UNEL-MEC motors, ensures long-term robustness and reliability, allowing for eventual replacement or repair of the motors, all of which are unified and built to international standards. Operating temperature: -25°C/+70°C
Key Features
- Protective cap made of weather-resistant laminated fiberglass
- External galvanized steel weatherproofing net, protected against weathering, according to UNI EN 294 standard
- Impeller with high-performance backward blades, made of welded and painted black sheet metal statically and dynamically balanced according to UNI ISO 1940/BS 6861/1
- Three-phase or single-phase asynchronous motor, EEF 1 and 2 efficiency, suitable for operation by speed regulation, IP 55 protection, class F insulation, S1 service, execution 5, conforms to IEC/EEC specifications
On request:
- TC MF: Version with single-phase motorization, Volts 230 Hz 50
- TC ATEX: Atex-certified version for potentially explosive environments
- TC 2V: Version with three-phase dual speed motorization
- TC HT: High temperature version
- TC INOX: Version with stainless steel impeller and base plate
Accessories
- Cerebro and/or Easy series electrical panel
- Speed controller (single-phase)
- Suction gravity damper
Technical characteristics
0,37
3PH
1,2
6
QE Cerebro / Easy
Dimensions
710X710x650
610X610
NO.4X9MM
323
60
CIMI Srl reserves the right to change dimensional dimensions and/or performance for improvements or range changes without what is on the site being binding.
The reported data meet the following parameters:
- - Tolerance on flow rate ±5%
- - Noise tolerance +3dB(A)
- - Air temperature 15°C
- - Barometric pressure 760 mm Hg
- - Air specific gravity 1.226 kg/m³
- - Frequency 50 Hz
Sound pressure level was measured by omnidirectional free-field measurement at 1.5 or 3 m (depending on the product) from the fan with ducted inlet, tolerances, performance points and environments according to European standards.
Flow rate tolerance ±5% | Noise tolerance +3dB(A) | Air temperature 15°C | Barometric pressure 760 mm Hg | Air specific gravity 1.226 Kg/m³ | Frequency 50 Hz
The sound pressure level was measured with omnidirectional free-field measurement at 1.5 or 3 m (depending on the product) from the fan with ducted inlet, tolerances, performance points and environments according to European standards."
- Protective cap made of weather-resistant laminated fiberglass
- External galvanized steel weatherproofing net, protected against weathering, according to UNI EN 294 standard
- Impeller with high-performance backward blades, made of welded and painted black sheet metal statically and dynamically balanced according to UNI ISO 1940/BS 6861/1
- Three-phase or single-phase asynchronous motor, EEF 1 and 2 efficiency, suitable for operation by speed regulation, IP 55 protection, class F insulation, S1 service, execution 5, conforms to IEC/EEC specifications
On request:
- TC MF: Version with single-phase motorization, Volts 230 Hz 50
- TC ATEX: Atex-certified version for potentially explosive environments
- TC 2V: Version with three-phase dual speed motorization
- TC HT: High temperature version
- TC INOX: Version with stainless steel impeller and base plate
The TC series is used for direct or ducted rooftop suction, wherever large volumes of air need to be moved with modest heads. The construction of this series, equipped with UNEL-MEC motors, ensures long-term robustness and reliability, allowing for eventual replacement or repair of the motors, all of which are unified and built to international standards. Operating temperature: -25°C/+70°C
- Cerebro and/or Easy series electrical panel
- Speed controller (single-phase)
- Suction gravity damper